TM 5-4120-374-13
5-8. COMPRESSOR (CONT)
LOCATION/TESTING
ACTION
REMARKS
TOP OF HOUSING
6. Compressor
a. Connect suction and discharge pressure gauges to the suction
and discharge service valves.
b. Open suction and discharge service valves.
c. Operate the air conditioner in the cooling mode and verify
that the normal operating pressures are as follows:
Normal Operating Pressures
Outdoor Ambient Temperature
95F(35C)
120F/125F(48.9C/57.7C)
At
90F/80F(32.2C/26.7C)DB/WB
return air to unit
6171 PSI
Suction Pressure
230260 PSI
Discharge Pressure
At  80F/67F(26.7C/19.4C)DB/WB  return  air  to  unit
4454 PSl
Suction Pressure
150175 PSl
Discharge Pressure
d. Stop air conditioner.
e. Close suction and discharge service valves.
f.  Remove gauges.
Disconnect input power source before performing this maintenance task.
g. Operate the air conditioner in the cooling mode and using a
multimeter, measure the insulation resistance of the compressor
internal motor windings at the start relay and selector switch.
h. Verify that the insulation resistance between the windings
and compressor frame is NOT less than 60 megohms.
i . Verify that the insulation resistance of the main winding
(terminal pin A to C) is between .6 and .8 ohms.
j.  Verify that the insulation resistance of the auxiliary winding
(terminal pin A to B) is between 5 and 7 ohms.
k. If testing indicates that the compressor is defective, remove
or repair compressor.
5-12