TM 5-4120-374-13
5-10. EVAPORATOR COIL (CONT)
REMARKS
ACTION
LOCATION/lTEM
HOUSING
INTERIOR
Test evaporator coil for leaks prior to discharging refrigerant system and removing
evaporator coil.
a. Remove two (2) screws at top of frame securing condenser
9. Evaporator Coil
shroud to frame.
b. Remove screw on top of frame securing suction line clamp.
c . Remove eight (8) screws securing frame to base.
d. Remove frame from base.
e. Remove air filter.
f. Unsolder suction line approximately two (2) inches below
header and remove suction line from evaporator coil.
g. Unscrew and remove flare nut between expansion valve and
evaporator coil.
h. Remove six (6) screws securing evaporator coil to bulkhead.
i . Remove four (4) screws from underside of base that secure
evaporator coil to base.
Remove evaporator coil.
5-24
|