TM5-4120-375-14
Table 5-1.
DIRECT SUPPORT MAINTENANCE TROUBLESHOOTING (cont.)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
COMPRESSOR RUNS BUT DOES NOT COOL.
Step 1.
Check sight glass for bubbles.
If bubbles exist leak check system in accordance
with paragraph 5-16.
Replace sight glass in accordance with
paragraph 5-33.
Step 2.
Install gauges in accordance with paragraph 5-21.
Step 3. Check
Check system pressure in accordance with
Table 5-2.
compressor for damaged valves.
Test compressor in accordance with paragraph
5-35.
5-6
|