TM-4120-375-14 THERMAL  EXPANSION  VALVE  (CONT.) LOCATION/ITEM ACTION REMARKS ADJUSTMENT 4. Thermal  Expansion  Valve g. 7. If the superheat setting is not within the limits shown above (higher than the values in Table 5-3), adjust  the  expansion  valve  as  follows: a. Remove the hexagonal seal cap from the side of the power assembly, and loosen the bonnet seal. b. Turn  the  adjusting  stem  two  complete turns to change superheat of one degree F. Turn  clockwise  to  raise,  and  counterclock- wise  to  lower,  the  superheat  setting. Do not turn more than two full turns, then wait ten minutes  for  temperature  to  stabilize  before observing  temperature  and  pressure  readings. c. When  the  proper  setting  is  obtained,  replace the screw cap and seal on the valve adjusting stem. d. If the expansion valve cannot be adjusted then stop the air conditioner and replace the expansion valve. Remove  the  thermometer  or  thermocouple  probe  from the suction line,   and  replace  the  insulating material. Close the suction service valve, remove the gauge, and install the cap on the service valve port. 5-56

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business