TM5-4120-375-14 QUENCH VALVE (CONT.) LOCATION/ITEM ACTION REMARKS REMOVAL 7. Quench  Valve WARNING All  refrigerant  gas  must  be  discharged  from  the  system  before  proceeding with the removal of the quench valve. NOTE Always  perform  inspection/test  and  adjustment  before  discharging  system to  remove  refrigeration  component. a. Discharge  the  system  in  accordance  with  paragraph 5-12. NOTE Note position of bulb on removal and be sure to replace in same position. b. Remove insulation (14) and band clamps from sensing bulb  (18). Carefully  detach  bulb  and  capillary tube. c. Remove two cap screws (15) securing the power assembly (16) to the flanged base (17). d. Remove the power assembly, capillary tube (19) and sensing bulb (18). 5-62