5-95 TM5-4120-375-14 CONDENSER COIL (CONT.) LOCATION/ITEM ACTION R E M A R KS REMOVAL 5. Condenser   Coil All   refrigerant   gas   must   be   discharged   from   the   system   before   proceeding with  the  removal  of  the  condenser  coil. NOTE Always   perfom   inspection/test   and   adjustment   before   discharging   system to   remove   refrigeration   component. a . b . c . d. e . Discharge paragraph system   in   accordance   with 5-12. Debraze   condenser   coil   (12)   in   accordance with   paragraph   5-15. Remove  two  countersunk  screws  (13)  and  two lock   nuts   (14)   securing   outside   upper condenser   coil   bracket   (15)   to   frame. Remove   two   screws   (16)   and   two   flat   washers (17)   securing   outside   upper   condenser   coil bracket   to   condenser   coil. Remove   outside   upper   condenser   coil   bracket.