TM5-4120-375-14
CONDENSER COIL (CONT.)
LOCATION/ITEM
ACTION
REMARKS
INSTALLATION
7.
Condenser Coil
u.
v .
w.
x.
y.
z.
a a.
bb .
Align outside lower condenser coil bracket
(20) to frame and condenser coil.
Secure outside lower condenser coil bracket
to frame with two countersunk screws (18) and
two lock nuts (19).
Secure outside lower condenser coil bracket to
condenser coil with two screws (21) and
two flat washers (22).
Align upper outside condenser coil bracket
(15) to frame and condenser coil.
Secure upper outside condenser coil bracket
to frame with two countersunk screws (13)
and two lock nuts (14).
Secure upper outside condenser coil bracket
to condenser coil with two screws (16) and
two flat washers (17).
Braze condenser coil (12) in accordance with
paragraph 5-15.
Leak check, evacuate and charge system in
accordance with paragraphs 5-17 thru 5-19.
5-103
|