TROUBLESHOOTING
---------------------------------------------------------------------------
TEST  OR  INSPECTION
CORRECTIVE  ACTION
----------------------------------------------------------------------
VENTILATION  MODE  ONLY
1.
AIR CONDITIONER FAILS TO OPERATE.
Be careful when working with high voltage.
Failure to comply can result in
serious injury or death.
Step 1.
Check to see if main
Connect  power
208VAC,  three
Step 2.
Check to see if main
power is plugged in.
cable  to  a  source  suppling
phase, 60 Hz. power.
power  connector  is  defective  in
accordance  with  paragraph  4-23.
Replace defective main power connector in
accordance  with  paragraph  4-23.
Step 3.
Check  for  loose  electrical  connections.
Tighten  electrical  connections.
Step 4.
Check  for  defective  wiring  in  accordance
4-24.
Step 5.
Check
with  paragraph
Replace defective wiring. Use identical
wire  consult  Appendix  F-and  solder  (Item  12,
table  D-1)  all  terminals  connectors  in
accordance  with  paragraph  4-24.
to see that selector switch is in FAN position.
Place selector switch in FAN position. If
the air conditioner will NOT operate check
for  a  defective  switch  in  accordance  with
paragraph  4-16.
Replace  defective  switch
in  accordance  with  paragraph  4-16.
4-13
 
 |