Page Title: TESTING/INSPECTION
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM5-4120-375-14 CONTROL BOX (CONT.) LOCATION/ITEM ACTION REMARKS TESTING/INSPECTION 6. Thermostat a. b. c. d. e. f. g. h. i. j. k. 1. m. n. Place thermostat in ambient temperature of 80 -90 F (28-32  C). Place  temperature  control  on  thermostat  in WARM position. Check for continuity between terminals COM and NC. If lack of continuity is found replace defective thermostat. Place temperature control on thermostat in the COOL position. Check for continuity between terminals COM and NO. If lack of continuity is found replace defective thermostat. Place thermostat in ambient temperature of 40 -50 F (4-10  c). Place  temperature  control  on  thermostat  in  the  WARM position. Check continuity between terminals COM and NC. If lack of continuity is found replace defective thermostat. Place  temperature  control  on  thermostat  in  the  COOL position. Check continuity between terminals COM and NO. If lack of continuity is found replace defective thermostat. 4-38

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business