TM5-4120-376-14
4-22. JUNCTION BOX AND CONTROL MODULE ASSEMBLY/Inspect, Test, Replace (Cont)
L O C A T I O N / I T E M
Installation:
Replay K4 and Relay K5 Assy
1. Align relay K4 and relay K5 assembly with holes in junction box.
2. Secure relay K4 and relay K5 with three lock nuts (57) and three flat washers (58).
3. Attach wires to appropriate terminals in accordance with Appendix E and remove tags.
Relay K2, K7 and K9
1. Align relays K2, K7 and K9 (56) with holes in junction box.
2. Secure relays K2, K7 and K9 to junction box with twelve screws (53) twelve flat washers
(54) and twelve lock nuts (55).
3. Attach wires to appropriate terminals in accordance with Appendix E and remove tags.
Relay K3
1. Align relay K3 (52) with holes in junction box.
2. Secure relay K3 to junction box with four screws (49) four flat washers (50) and four lock
nuts (51).
3. Attach wires to appropriate terminals in accordance with Appendix E and remove tags.
Terminal Board TB1
1. Align terminal board TB1 (47) and marker strip (48) with holes in junction box.
2. Secure terminal board TB1 with four screws (44) four flat washers (45) and four lock nuts
(46).
3. Attach wires to appropriate terminals in accordance with Appendix E and remove tags.
Terminal Board TB3
1. Align terminal board TB3 (42) and marker strip (43) with holes in junction box.
2. Secure terminal board TB3 with four screws (39) four flat washers (40) and four lock nuts
(41).
3. Attach wires to appropriate terminals in accordance with Appendix E and remove tags.
4-117
|