TM5-4120-376-14
4-25. LOUVER AND CONDENSER FAN HOUSING ASSY/Inspect, service, Adjust, Repair,
Replace (Cont)
LOCATION/ITEM
Inspection:
Inspect for bends, cracks or weather damage, replace if damaged.
Service:
WARNING
Dry cleaning solvent, P-D-680 or P-S-661, used to clean parts is potentially
dangerous to personnel and property. Avoid repeated and prolonged skin
contact. Do not
is 100°F (38°C).
Wipe consenser louver
use near open flame or excessive heat. Flash point of solvent
with cloth dampened with dry cleaning solvent (Table D-1, Item 3).
Adjust:
1. Turn off air conditioner and wait four hours or until air conditioner is uniformly at
ambient temperature or head pressure is below 150 psig (10.516 kg/cm 2).
2.
3.
4.
Loosen mechanical post screw (13).
Close condenser louvers (14).
Pull control cables (15) tight and tighten mechanical post screw (13).
4-153
|