TM5-4120-376-14
5-18. CONDENSER LOUVER ACTUATOR AND CONTROL ASSY/Service, Adjust, Replace
(Cont)
LOCATION/ITEM
CABLE ACTUATOR
Removal:
WARNING
Purge system with dry nitrogen prior to soldering. Refrigerant heated to
1200°F (649°C) creates phosegene gas.
WARNING
Avoid contact with refrigerant acid. Burns could result from contact with
refrigerant.
NOTE
Leak check fittings.
NOTE
Always perform inspections, adjustments and test before removing refrigerant
components.
10. Discharge system in accordance with paragraph 5-8, page 5-10.
11. Remove flare nut (7) cable actuator (10).
12. Remove two flat nuts (8) and two lock washers (9) and condenser cable actuator (10) from
actuator mounting bracket (11).
5-26
|