| |
TM5-4120-376-14
5-22. COMPRESSOR, ACCUMULATOR AND RELATED PARTS/Replace (Cont)
LOCATION/ITEM
Removal:
3. Remove fourteen screws (7) and front cover (8) from housing.
4. Remove seven screws (9) and center cover (6) from housing.
5. Remove louver cable actuator in accordance with paragraph 5-18, page 5-24.
6. Remove condenser fans, motors, and support assemblies in accordance with paragraph
4-15, page 4-39.
7.
8.
9.
10.
11.
Remove condenser motor support in accordance with paragraph 5-17, page 5-21.
WARNING
Purge system with dry nitrogen prior to soldering. Refrigerant heated to
1200° F (649° C) creates phosegene gas.
WARNING
Avoid contact with refrigerant acid. Burns could result from contact with
refrigerant.
CAUTION
Maintain a 1-2 cpm (0.1-0.2 M 3 Min) flow of dry nitrogen through the
refrigeration system to prevent oxidation and scaling when brazing or debrazing
components.
Leak check fittings.
removing refrigerant
NOTE
Always perform inspections, adjustments and test before
components.
Disconnect electrical connector P-7 (10) from compressor (11).
Discharge system in accordance with paragraph 5-8, page 5-10.
Deb raze compressor in accordance with paragraph 5-9, page 5-11.
Remove four bolts (12) and four lock washers (13) and compressor from housing.
5-63
|