5-22. COMPRESSOR, ACCUMULATOR AND RELATED PARTS/Replace (Cont)
LOCATION/ITEM
Installation:
CAUTION
Maintain a 1-2 cpm (0.1-0.2 M3 Min) flow of dry nitrogen through the
refrigeration system to prevent oxidation and scaling when brazing or debrazing
components.
1. Align compressor (11) and compressor mounting bushing (14) with housing and secure
compressor and compressor mounting bushing to housing with four bolts (12) and four lock
washers (13).
2.
3.
5-10
4.
Braze in accordance with paragraph 5-10, page 5-12.
Test, evacuate and charge system in accordance with paragraphs 5-8 through 5-14, pages
through 5-19.
Connect electrical connector P-7 (10) to compressor.
5. Install condenser fans, and support assemblies in accordance with paragraph 4-15, page
4-46.