TM5-4120-376-14
5-22. COMPRESSOR, ACCUMULATOR AND RELATED PARTS/Replace (Cont)
LOCATION/ITEM
ACCUMULATOR
Removal:
1. Remove three screws (1) three lock
washers (2) and fabric cover (3) to rear
cover (4) from housing.
2. Remove fourteen screws (5) and
rear cover to center cover (6) from
housing.
3. Remove condenser louver cable
actuator in accordance with
paragraph 5-18, page 5-24.
4. Remove condenser fans, motors
and support assemblies in
accordance with paragraph 4-15, page
4-39.
WARNING
Purge system with dry nitrogen prior to soldering. Refrigerant heated to
1200° F (649°C) creates phosegene gas.
WARNING
Avoid contact with refrigerant acid.
Burns could result from contact with
refrigerant.
CAUTION
Maintain a 1-2 cpm (0.1-0.2 M 3
Min) flow of dry nitrogen through the
refrigeration system to prevent oxidation and scaling when brazing or debrazing
components.
5-69
|