M-Monthly
TM5-4120-376-14
Table 4-1. ORGANIZATIONAL PREVENTIVE MAINTENANCE CHECKS AND SERVICES
(PMCS) (Cont)
Q-Quarterly
S-Semiannually
ITEM
NO.
5
6
7
8
INTERVAL
ITEM TO BE
EQUIPMENT IS NOT
M
Q
S
INSPECTED
PROCEDURE
READY/AVAILABLE IF:
NOTE
Check after air conditioner has been running (cool mode) for 15 minutes.
Sight Indicator (5)
Fresh Air Filter (6)
Auxiliary Power (7)
Receptacle (J-12)
Condenser Coil
Guard (8)
Check to see that
sight indicator is
clear of bubbles
and center dot
green.
Check for dirt
or damage.
Check for any
loose connec-
tions or damage.
Check for dirt
or damage.
If sight indicator has bubbles
or center dot is yellow notify
Direct Support Maintenance.
Replace fresh air filter in
accordance with paragraph
4-13, page 4-33.
If damaged repair or replace
auxiliary power receptacle
(J-12) in accordance with
paragraph 4-23, page 4-134.
[f damaged replace condenser
veil guard in accordance with
paragraph 4-14, page 4-34.
4 -9
|