TM5-4120-376-14
Table 4-2. ORGANIZATIONAL MAINTENANCE TROUBLESHOOTING (Cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 4.
Remove eight screws (4) securing access cover (charging box) to housing.
Remove access cover (5).
Check to see if low and high pressure switches (6) contacts are open.
Push reset button on the low and high pressure switches. If compressor does not
start after a short delay, stop air conditioner. Notify Direct Support Maintenance.
4-18
|