5-27.
TM5-4120-377-14
For inspection and cleaning of installed coil, see paragraph 4-68.
Preliminary procedures:
1. Remove receiver. (See para 5-25.)
2. Remove condenser coil guard. (See para 4-26.)
Figure 5-28.
Condenser Coil
a. Removal
(1) Observe position of tubing from condenser for ease of reassembly.
(2) While purging the system with nitrogen, debraze the remaining tube joints to the condenser. (See para
5-7 and 5-8.)
When handling coils, wear gloves to avoid cuts and reduce fin damage on coil.
(3) Using screwdriver, remove four pan head screws from each side while supporting condenser coil.
(4) Using screwdriver, remove the eight flat head screws from the front flanges of the coil.
(5) Using gloves to protect your hands and coil fins, carefully slip the coil and brackets from unit.
5-55
|