TM5-4120-383-14
Table 2-1.
OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES
Continued
Interval
Item
Procedures
Item To Be
Equipment Is
BDAWM
No.
Not Ready/
Check for and have
Inspected
Available If:
repaired or adjusted
as necessary.
7
Fresh Air
Check for proper
Damper
adjustment.
Freedom of
Control wheel
missing or
operation.
inoperable.
8
Condensate
No water dripping
Water is
Drain
leaking in an
anywhere except
drain.
area that
would cause
damage or be
a hazard.
9
Inspect for damage,
Control
Control
Module
secure mounting, and
module
proper operation in
damaged or
operating
accordance with
improperly.
10
Refrigerant
After 15 minutes of
Bubbles,
milky flow,
Sight Glass
operation in maximum
cooling, check for
or yellow
color is
bubbles or milky
observed.
flow indicating low
refrigerant charge.
Check for yellow
color which indicates
presence of moisture.