TM5-4120-383-14
4-32.
TRANSFOMER,
RECTIFIER,
CAPACITORS,
AND
HARNESS.-Continued
NOTE
The ohmmeter test does not show the behavior of a
capacitor under load. Such testing requires special
equipment which is not economically practical for
If breakdown under load is
testing small capacitors.
suspected replace the capacitor.
Replace.
c.
(1)
Transformer.
(a) Tag and disconnect wire leads.
(b) Remove four screws and lock washers and pull
transformer from unit.
(c) Attach transformer to unit with four screws and lock
washers.
(d) Slip heat shrinkable insulation tubing on ends of wires
to be soldered.
(e) See wiring diagram figure 4-4 and tags and connect all
wire leads. Remove tags.
(f) Slip heat shrink tubing over all exposed solder
connections and shrink in place.
(2)
Rectifier/Capacitors.
(a) Tag and disconnect wire leads.
(b) Remove two screws and pull rectifier from unit.
(c) Remove capacitors.
(d) Install capacitors.
(e) Attach rectifier to unit with two screws.
(f) See wiring diagram figure 4-4 and tags and connect all
wire leads. Remove tags.
(3) Install junction box and control module. (See para 4-21
and 4-27.)
(4) Install top front cover (para 4-11).
(5) Connect power at power source.