4-39.
LOW PRESSURE CUTOUT SWITCH (LPCO) JUMPER.-Continued
a.
Disassemble.
(1) Disconnect power at power source.
(2) Remove control module and junction box (para 4-21 and
4-27).
It is not necessary to totally remove all wire connections
and capillary line so long as the junction box can be pulled out
enough to gain access to the pressure switches. Support the
junction box so that wires and capillary line are not damaged.
(3) Remove top front cover (para 4-11).
(4) Install jumper wire (20 AWG minimum) between terminals 1
and 2 of low pressure cutout switch. Check that jumper will not
short out against frame of control panel.
(5) Fabricate CAUTION tag (shown below) to place on control
panel to show that low pressure cutout switch has been bypassed.
CAUTION
Air conditioner low pressure cutout switch (S5)
has been bypassed.
Compressor will not shut off
under low suction pressure conditions.
CAUTION TAG EXAMPLE
Assemble.
b.
(1) Install junction box and control module (para 4-21 and
4-27).
(2) Install top front cover (para 4-11).
(3) Connect power at power source.
NOTE
Remove the LPCO jumper when outside air temperature
increases to 40F (5C).
4-109
|