TM5-4120-383-14
5-29.
CONDENSER
COIL.-Continued
(7) Disconnect flare nut nearest the sight glass from
(8) Remove sight glass mounting plate.
(9) Remove clamps from the receiver.
(10) Debraze reducer coupling from lower connection on the
coil.
(11) Debraze reducer coupling from upper connection on the
coil.
When handling coils wear gloves to avoid cuts and
reduce fin damage.
(12) Carefully lift condenser coil and receiver up and out of
unit.
(13) Place old coil along side of new coil so that the
receiver can be debrazed and brazed to the new coil.
If coil is defective replace it.
b.
Replace.
c.
Installation.
(1) Remove (debraze) receiver. Braze receiver to new coil.
When handling coils wear gloves to avoid cuts and
reduce fin damage.
(2) Carefully place coil into position in unit.
(3) Align holes and secure the coil and condenser air inlet
guard with six pan head screws through back of unit housing.
(4) Braze lower and upper reducer couplings with attached
hardware to coil.
(5) Replace dehydrator with a new one and connect flare
fittings.
(6) Install receiver clamps and sight glass mounting plate.
(7) See paragraph 5-32 and install compressor.
5-68
|