|
|
TM5-4120-383-14
5-32.
COMPRESSOR.-Continued
When a hermetic motor burns out, the stator winding
decomposes forming carbon, water and acid which
contaminates refrigerant systems. These contaminates
must be thoroughly removed from the system to prevent
repeated motor failures. Motor burn out may also
cause damage to the air conditioner electrical
system.
The following clean up procedures must be
followed in any case of compressure motor burnout.
(i) Perform removal procedure (step (3), preceding page).
(j) Remove the dehydrator (para 5-30). Do not replace with
a new dehydrator at this time.
(k) Flush the refrigerant system with refrigerant solvent
R-114 dichlorotetrafluroethane (National Stock Number 6830-00-782-
6512).
Flushing should be done under a pressure of 8 to 12 psig
2
(.56 to .84 kg/cm ), using a pump of approximately 1/3 horsepower.
The R-114 may be recirculated if run through a 10 micron filter.
Procedures for flushing the system are as follows:
Refer to figure 5-22 and connect the discharge line
q
of the pump to the tubing at point 1. Connect the
recovery line to the tubing at point 2.
Leave the
suction line service valve (point 3) closed. Cap
the tubing at points 4 and 5.
Start the pump and flush the line for approximately
q
10 minutes then turn the pump off.
Remove the recovery line from point 2 and cap the
q
tubing at point 2.
Connect the recovery line to the valve at point 3
q
and open the suction line service valve.
Start the pump and flush the line for approximately
q
10 minutes, then turn the pump off.
Disconnect the bypass solenoid valve plug P8 from
q
receptacle J8.
5-77
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |