TM 5-4120-386-14
Table 2-1. Operator Preventive Maintenance Checks and Services (PMCS)
Continued.
Note: Within designated intervals, these checks aretobe performed inthe order listed.
B-Before Operation
D-During Operation
A - A f t e r Operation
I t e m Interval
Item to be
Procedures:
Equipment
No.
B D A Inspected
is not ready/
available if
7
-
Condenser Louver
Louver re-
Check for insecure
q
q
mountings and damaged
quires clean-
louver blades. Report
ing, is ob-
structed,
damaged condition to
organizational maintenance
damaged, or
personnel.
loose.
8
-
Information Plates
Plates are
Check for security and
q
q
loose or
illegible.
9
-
Condensate Drain
Inspect drains for
Obstructions
q
q
Tubes
obstructions. Remove
cannot be
removed.
obstructions as required.
l0
Insure knobs are in place
Control Module
Knobs are
missing or
and check to see that
switches function
switches do
properly. Report damaged
not function
condition to
properly.
organizational
maintenance personnel.
11
Liquid Sight
After approximately five
Moisture or
Indicator
minutes of operation,
low charge is
check for moisture and
indicated, or
low refrigerant charge.
if indicator
is cracked.
Yellow indicates moisture;
bubbles or milky
appearance indicates low
charge. Report abnormal
condition to direct support
maintenance personnel.
2-4
|