TM 5-4120-386-14
Table 4-1. Organizational Preventive Maintenance Checks and Services (PMCS)-
Continued.
W-Weekly
Q-Quarterly
Interval
Item
Item to be
Procedures:
Equipment
No. W
Inspected
is not ready/
Q
available if
2
Evaporator Inlet
a.
Slide air filter out
Filter is
Filter and
of the retaining
damaged,
Evaporator Inlet
clips.
missing, or
Louver
clogged.
b . Inspect air filter
for damage. Replace
if damaged.
c. Clean air filter with
running water.
d. Inspect louver for
bent blades.
Straighten or replace.
e. Slide air filter into
evaporator inlet louver.
f. Install evaporator
inlet louver.
3
a . Remove top cover.
Items are
Mist Eliminator
and Evaporator
b. Slide mist eliminator
damaged,
missing, or
Outlet Louver
out of the mist
eliminator holder.
clogged.
. Inspect mist
eliminator for damage.
Replace if damaged.
Dry cleaning solvent (Item 16, App. D) used to clean parts is potentially
dangerous to personnel and property. Avoid repeated and prolonged skin
contact. Do not use near open flame or excessive heat. Flash point of
solvent is 100oF (38oC).
d . Clean mist eliminator
with dry cleaning
solvent.
e . Lubricate mist
eliminator with
filter-kote (Item 17,
excessive oil.
f.
Install mist eliminator
in holder.
4-7
|