TM 5-4120-386-14
4-18. EVAPORATOR LOUVERS-Continued,
REMARKS
LOCATION/ITEM
ACTION
CLEAN
a.
Inspect louver blades for bends
3. Evaporator
or damage and straighten.
Inlet and
b. Inspect for missing or damaged
Evaporator
Outlet
tabs, (9) and filter clips (5).
Inlet Louvers
Louvers
Clean parts in well ventilated area. Avoid inhalation of solvent
fumes and prolonged exposure of skin to cleaning solvent. Wash
exposed skin thoroughly. Dry cleaning solvent, P-D-680, used
to clean parts is potentially dangerous to personnel and
property. Avoid repeated and prolonged skin contact. Do not
use near open flame or excessive heat. Flash point of solvent is
100F to 138F (38oC to 59oC).
c.
Clear obstructions from louver
blades using dry cleaning solvent.
d. Clean louver blades of
obstructions.
INSTALLATION
4. Evaporator
a.
Install evaporator inlet air filter
Evaporator
Inlet
(4) into filter clips (5).
Inlet Louver
Louver
b. Aline and secure louver (3) to
Only.
housing using eight screws (1)
and eight lockwashers (2) respec-
tively.
Aline and secure louver (8) to
Evaporator
5. Evaporator
housing using six screws (6)
Outlet
Outlet Louver
and six lockwashers (7) respectively.
Louver
Only.
4-27
|