TM 5-4120-386-14
4-22. FRESH AIR DAMPER AND ACTUATOR-Continued.
REMARKS
LOCATION/ITEM
ACTION
Position control actuator (13)
Adjustment
a.
to fully closed position.
b.
Loosen screw (1) from
mechanical post (12) of fresh
air damper.
Position fresh air damper to
c.
fully closed position by hand
while looking down vent housing
from evaporator fan motor compart-
ment with flashlight.
d.
Tighten screw (1) on mechanical
post (12).
e.
Shine flashlight into fresh air
damper screen side of unit (read
side) while looking into vent
housing from evaporator fan motor
compartment. Ensure no light can
be seen around edges of damper seal.
If fails, repeat adjustment proce-
dure. If fails again, Service or
Replace fresh air damper as
necessary.
f.
Install evaporator inlet and
See paragraph
outlet louvers.
Install top covers.
See paragraph
g.
4-42
|