TM 5-4120-386-14
5-12. REFRIGERATION SYSTEM SERVICING - (BRAZING/DEBRAZING) - Continued.
LOCATION/ITEM
ACTION
REMARKS
Debrazing. Debraze joints
c.
for removal of refrigeration
system components as follows:
All refrigerant-22 must be dis-
charged from the system and the
entire system must be purged with
dry nitrogen before begiming
any debrazing operation.
( 1 ) Determine which
joints are to be
debrazed. Due to the
limited work space
inside the air
conditioner, it may be
more convenient to
remove a part of the
inter-connecting tubing
with the component
rather than debrazing
the joints on the
component itself.
(2) Before debrazing a joint
on a valve, disassemble
the valve to the extent
possible, then wrap all
but the joint with a wet
rag to act as a heat sink.
The polyurethane foam used as
insulation in the air conditioner
will break down to form toxic
gases if exposed to the flame of a
torch at brazing temperature.
5-39
|