5-12. REFRIGERATION SYSTEM SERVICING - (BRAZING/DEBRAZING) - Continued.
REMARKS
LOCATION/ITEM
ACTION
e.
Reassembly. If tubing
sections or fittings were
removed with a component,
debraze them from the
component, clean the joints,
and braze them to the new
component before
reinstallation.
f.
Brazing. Braze joints within
the air conditioner as follows:
( 1 ) Position the component
to be installed.
(2) To prepare a joint on a
valve for brazing,
disassemble the valve to
the extent possible.
Then wrap all but the
joint with a wet rag to
act as a heat sink.
( 3 ) Protect insulation,
wiring harnesses, and
surrounding components
with appropriate shields.
(4) Be sure the work area is
well ventilated and that
dry nitrogen is flowing
through the refrigeration
system at a rate of less
than 1-2 cfm
(0.3028-0.057
m /minute).
( 5 ) Apply sufficient heat
uniformly around the
joint to quickly raise it
to a temperature that
will melt the filler
alloy. Remove heat as
soon as brazing is
completed.