5-20. SOLENOID VALVES-Continued.
REMARKS
ACTION
LOCATION/ITEM
Removal
1. Solenoid L2
Disconnect electrical connector
a.
from bulkhead.
Remove plunger nut (1) and name-
b.
plate (2) from plunger (4) and
remove coil (3).
Remove two screws (5), two nuts
c.
(6), and two spacers (7) securing
the valve body to the housing,
See Para. 5-11.
Purge system.
d.
See Para. 5-12.
Debraze and remove valve.
e.
2. Solenoid L1
Disconnect electrical comector
a.
of solenoid coil from bulkhead.
Remove plunger nut (1) and name-
b.
plate (2) from plunger (4) and
remove coil (3).
Remove two screws (5), two nuts
c.
(6), and two spacers (7) securing
the valve body to the housing.
See Para. 5-11.
Purge system.
d.
See Para. 5-12.
Debraze and remove valve.
e.
5-70
|