TM5-4120-387-14
TABLE 4-2. TROUBLESHOOTING (Cont.)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 10.
Check operation of compressor run capacitor (C2).
Test capacitor.
(See para 4-52.) Replace if defective.
Step 11.
Check operation of compressor (Bl).
If not operating, notify your supervisor and Direct Support
Maintenance.
3.
COMPRESSOR STARTS NORMALLY, BUT COMPRESSOR CIRCUIT BREAKER SOON TRIPS.
Step 1.
Check to be sure fabric cover is rolled up.
Roll up and secure fabric cover.
Step 2.
Check to be sure there is no restriction to air flow through
condenser section.
Clean all obstructions from condenser inlet, outlet, and conden-
ser coil.
4-35
|