4-59. CONDENSER FAN
Preliminary procedure:
Remove condenser air discharge guard.
(See para 4-20.)
Figure 4-58. Condenser Fan
a.
Removal
(1) With hex head wrench, loosen set screw in fan hub.
(2) Carefully pull condenser fan off of motor shaft.
(3) Remove shaft key and shims (if applicable) or tape in place so they
will not be lost.
b.
Inspection
(1) Check fan for dents, bent or loose blades, and that the hub is securely
attached.
Replace if damaged.
(2) If motor problem is suspected, inspect or test motor per paragraph 4-60.
4-141
|