TM5-4120-387-14 (4) Remove bracket, spacer and gasket. (5) While purging the system with nitrogen, debraze the tubing. (See para 5-7 and 5-8.) (6) Remove liquid sight indicator. c. Installation NOTE Do not disassemble liquid sight indicator. (1) Position liquid sight indicator on tubing. (2) While purging the system with nitrogen, braze the tubing  joints.  (See para 5-7 and 5-8.) (3) With screwdriver,    install bracket, spacer and gasket with two screws and washers. (4) Replace the dehydrator. (See para 5-13.) (5) Replace charg (6) Leak test all para  5-9.) ing  valves. (See para 5-17.) newly connected joints and those in the repair area. (See (7) Evacuate and charge the refrigerant system.  (See para 5-10 and 5-11.) Follow-on procedure: 1. Install fan relay (K7).  (See para 4-54.) 2. Install top panel. (See para 4-23.) 5-57