Page Title: TABLE 3-1. TROUBLESHOOTING (Cont.)
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM5-4120-387-14 TABLE   3-1.   TROUBLESHOOTING   (Cont.) MALFUNCTION TEST OR INSPECTION CORRECTIVE  ACTION Step 6. With unit operating in COOL mode,    check  condition  of  refrigerant  in sight  glass. If indicator color is in the yellow zone or numerous bubbles appear in window,   turn selector switch to OFF and notify your supervisor  and  Direct  Support  Maintenance. 5. REDUCED HEATING CAPACITY. Step 1. Check that all doors, windows,   and other openings in the room or enclosure are tightly closed. Tightly close all openings. Step 2. Check  operation  of  Temperature  control  thermostat. Set  control  to  fully  INCREASE;  then,  if  condition  improves, adjust properly. 3-11

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing