1-11. Equipment Data.
Operating Temperatures:
Low..............................................................................-50F (-45 C)
High .............................................................................+120F (+49 C)
Performance:
Cooling Capacity ..........................................................60,000 Btu/hr
Heating Capacity ..........................................................47,000 Btu/hr
Power Required:
Voltage.........................................................................208
Phase ..........................................................................3
Hertz ............................................................................50/60
Amperage ....................................................................42
Dimensions:
Width ...........................................................................34.75 in. (88.27 cm)
Depth...........................................................................23.50 in. (59.69 cm)
Height ..........................................................................65.20 in. (165.61 cm)
Weight .........................................................................600.00 lb. (272.16 kg)
Refrigerant:
Type ............................................................................R-22
Charge.........................................................................9.1 lbs (4.13 kg)
1-12. Safety, Care, and Handling. Read and understand all instructions relating to the specific function you are to
perform before starting task.
a. Carefully read and understand all notes, cautions, and warnings contained in this manual that pertain to the task
you are to perform.
b. Carefully read and understand all WARNING and CAUTION plates located on the air conditioner.
c. Never operate the air conditioner with any cover, screen, or panel removed unless the instructions specifically
instruct you to do so. Then do so only with extreme caution.
d. Carefully plan all maintenance tasks and never take unnecessary risks.
1-7