TM 5-4120-393-14
OPERATOR'S CONTROLS REAR
2-3. Indicators. The refrigerant sight glass is the only visual indicator used. Liquid refrigerant actually flows through the
sight glass chamber only during cooling cycles when the air conditioner is in operation in the COOL mode. The unit must
be operated approximately 15 minutes at maximum cooling with an ambient temperature higher than 70F (21C) prior to
checking the condition of the refrigerant at the sight glass. The sight glass is equipped with a center indicator that is
moisture sensitive. Dry refrigerant is indicated by green, it turns chartreuse when the moisture content becomes
undesirable, and yellow when the level becomes unacceptable. Excessive moisture in the refrigerant may damage or
possibly destroy the compressor. If the liquid refrigerant observed in the sight glass has an opaque, milky appearance, or
frequent bubbles appear, the volume of refrigerant is low and the system should be charged. Either moisture or low
charge indications should be reported to direct support maintenance.
CAUTION
Do not operate the air conditioner in the COOL mode if refrigerant color has
reached the yellow band or if numerous bubbles appear in the sight glass. COOL
mode operation may be continued with the refrigerant color in the chartreuse band
or with only an occasional bubble appearing in the sight glass, but the sight glass
should be checked every four hours to insure that the condition has not become
worse.