Table 2-1. Operator Preventive Maintenance Checks and Services
Procedures:
Interval
Check for and have
Equipment is
Item
Item to be
repaired or adjusted
Not Ready/
No.
BDAWM
Inspected
as necessary
Available If:
6
Fresh Air
Check for proper adjustment.
Damper
Check for freedom of operation.
Control kno bs
missing or
inoperable.
7
Control Panel
Check for obvious damage and missing
Control panel
knobs.
damaged.
Check for proper operation.
Unit not operating
properly.
8
Refrigerant Sight
After 15 minutes of operation at max-
Bubbles, milky flow
Glass
imum cooling with ambient temperature
or yellow color is
higher than 70 F (21C), check for
observed.
bubbles or milky flow indicating low
refrigerant charge. Check for yellow
color which indicates presence of
moisture.
2-6
|