4-33.
Fresh Air Damper (cont)
9.
Using two wrenches, secure link arm (13) to gear arm assembly (18) with a cap screw (9), spacer (10), flat washer
(11), and nut (12).
10. Using screwdriver, secure damper door (8) hinges to casing with eight screws (6) and lock washers (7).
11. Using two wrenches, connect link arm (5) to bracket on damper door (8) with a cap screw (1), bushing (2), flat washer
(3), and nut (4).
12. Using alien wrench, tighten setscrew (25) in adjusting knobs (26) on rod (32).
NOTE
FOLLOW ON MAINTENANCE:
1.
Install fresh air filter and frame. See para 4-31.
2.
Install conditioned air filter(s). See para 4-30.
3.
Install conditioned air intake grille(s). See para 4-22.
4.
Connect power.