4-57. Heater Thermostat (S3)
This task covers:
a. Removal
c. Installation
b. Testing
Initial setup.
Tools:
Tool kit, service, refrigeration unit NSN 5180-00-596-1474
Multimeter NSN 6625-00-553-0142
Personnel: 1
Equipment condition:
1. Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power cable
to air conditioner.
2. Remove mist eliminator. See para 4-32.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
REMOVAL
1.
Tag and disconnect leads.
2.
Using screwdriver and wrench, remove two screws (1), washers (2), and nuts (3).
3.
Remove thermostat (4).
TESTING
1.
With thermostat at room tem perature, use a multimeter set on the lowest OHMS scale to check for continuity between
each pair of contacts (4 and 6, 4 and 5, and 5 and 6).
2.
If continuity is not indicated between all contacts, replace the thermostat.