4-60. Condenser Fan Motor (B2) (cont)
NOTE
If all of the above inspections and tests are satisfactory, but the motor will still not
operate properly, notify Intermediate Direct Support Maintenance, who may desire
to make further tests before the motor is removed.
REMOVAL
1.
Disconnect motor cable connector.
2.
Support or hold motor (5) in place.
3.
Note quantity and location f shims prior to removing hardware in net step
4.
Using two wrenches, remove four cap screws (1), washers (3), nuts (2), and shims (4) from the motor (5) mount.
5.
Lift motor (5) through one of the condenser fan openings.
INSTALLATION
1.
Lift motor (5) into position through one of the condenser fan openings.
2.
Align motor mounting holes and reinstall shims (4) in same location as noted in step 3 of REMOVAL.
3.
Using two wrenches, secure motor (5) and shim (4) to mount with four cap screws (1), washers (3), and nuts (2).
4.
Install fans. See para 4-59.
5.
Spin fans and check for interference. Adjust fans in or out on shaft. Adjust motor front to rear by loosening mounting
screws.
6.
Connect P2 harness connector to motor.
4-138
|