TM 5-4120-393-14
5-30. Condenser Air Discharge Louvers and Linkage
This task covers:
a. Removal
c. Installation
b. Inspection
Initial setup.
Tools:
Tool kit, service, refriger ation unit NSN 5180-00-596-1474
Personnel: 1
Materials:
Rags (Appendix E, item 9)
Equipment condition:
1.  Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power cable
to air conditioner.
2.  Remove condenser coil. See para 5-22.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
REMOVAL
1.
Using screwdriver and wrench, remove screw (1), nut (2), and two flat washers (3) from actuator linkage (4).
2.
Remove push on nut (8) and remove linkage assembly (5), (6), (7), and (9) as an assembly from unit.
3.
Carefully flex the damper blades (10) enough to free the shorter (top) tab and remove damper blades (10).
4.
Remove bearings (11).
5.
If disassembly of the linkage parts is required, use a drill bit slightly smaller than the body diameter of the rivet (5).
Drill the rivet (5) out and remove the damper control (7), louver arm blades (9), and flat washers (6).
5-78