Click here to make tpub.com your Home Page

Page Title: Leak Checking Refrigeration System
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4130-234-13&P
f. Crack the refrigerant bottle valve to purge the hose
2-5.
Evacuation of Refrigeration System
assembly of air, then tighten hose assembly fitting on valve
a. Open  suction  and  receiver  valves  of  the
(12).
refrigeration system and purge system with dry nitrogen.
g. Open valve (12) and refrigerant bottle valve.
b. Connect hose assembly (8, fig. 2-4) with gaskets
h. Fill reservoir to desired level as indicated on scale
(2, 3) between refrigeration system receiver valve and
(8); slowly open valve (5) as required to expedite filling.
valve (14, fig. 2-3).
c.  Connect hose assembly (9, fig. 2-4) with gaskets
WARNING
(2, 3) between refrigeration system suction valve and union
d. Open refrigeration system receiver and suction
Exercise care in disconnecting hose
valves, and open valves (1, 2).
assembly from refrigerant bottle and
e. Set circuit breaker (22) to ON and switch (21) to
valve to prevent refrigerant from getting
VAC ON.
in the eyes or permanent damage to the
NOTE
eyes may result.
Application of heat to refrigeration system
i.  Close valves (5, 12) and refrigerant bottle valve.
will expedite evacuation.
Disconnect hose assembly and cap valves (5, 12).
f.  Evacuate refrigeration system for two hours to 200
microns or lower as indicated on gage (26).
2-4.
Leak Checking Refrigeration System
NOTE
a. Pressurize refrigeration system to approximately
To  determine  level  of  vacuum  in
15 psig, using dry nitrogen and refrigerant or refrigerant.
refrigeration system, close valve (2) and
b. Connect refrigeration system charge valve to union
observe indication of gage (26).
(18), using hose assembly (6, fig. 2-4) with gaskets (3, 4).
g. At end of the two hour evacuation period, close
c.  Connect leak detector (11) to connector (19, fig. 2-
refrigeration system suction and receiver valves.  Set
3).
switch (21) and circuit breaker (22) to OFF.
d. Ventilate area -of refrigeration system to be leak-
h. Remove hose assemblies and proceed directly to
checked.
charging  refrigeration  system  with  oil  or  charging
e. If leak detector is being used for the first time,
refrigeration system with refrigerant.
remove and discard screw from cap of REFERENCE LEAK
bottle and allow REFERENCE LEAK to stabilize for 15
2-6.
Charging Refrigeration System with OIL
minutes. Make certain REFERENCE LEAK bottle contains
CAUTION
a quantity of refrigerant, as observed through window in
Use care in storage and handling of
chassis.
refrigeration oil to prevent absorption of
f.  Point probe of leak detector toward floor and
moisture
and
other
atmospheric
observe airflow ball, located in probe; ball must rise and
float above tip of probe.  If ball fails to rise, tap probe
a. Uncap and open valve 16).
lightly to make certain ball is not stuck.
b. Open valves (1, 2), cap union (25), and uncap
g.  Set leak detector SENSITIVITY switch to LOW
union (24).
(used when element is new and when detecting large
c.  Connect hose assembly (6, fig. 2-4) between union
leaks), place tip of probe close to opening in REF LEAK
(24, fig. 2-3) and valve (6), using a 1/2 X 3/8 inch reducer
cap, and adjust BALANCE control until neon lamp in probe
on union (24).
just ceases flashing.
d. Cap and close valve (11).
h. Hold leak detector probe as close as possible to
e. Connect hose assembly (6, fig. 2-4) with gaskets
the area being checked and move the tip at a rate no
13, 4) between valve (11, fig. 2-3) and container filled with
greater than one inch per second along seams and joints
refrigeration oil.
suspected of leakage. When the probe encounters a leak,
f.  Set circuit breaker (22) to ON and switch (21) to
the flashing rate of the neon lamp will increase and will
VAC ON.
continue to flash at the faster rate as long as the probe is
g. Observe gage (26) until reading is slightly below
held near the leak.
1000 microns; then close valve (1). Slowly open valve (11)
and observe scale on beaker (4) until oil level reaches
1000 ML graduation. Close valves (6, 11).
2-8

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business