TM 55-8145-221-14&P
0027 00-1
Change 1
RECORDING THERMOMETER ELEMENT REPLACEMENT
0027 00
THIS WORK PACKAGE COVERS:
Removal and Installation
INITIAL SET-UP:
Maintenance Level:
Unit
Tools:
Equipment Condition:
General Mechanics Tool Kit (Section III, Item 1, WP 0048 00)
Refrigeration Unit shut down (WP 0006 00)
Portable Drill (Item 2,WP 0048 00)
Generator Set shut down (WP 0006 00)
Drill Bit Set (item 2, WP 0048 00)
Material/Parts:
Drive Rivets (5) (Item 17, WP 0081 00)
Sealant (Item 15, WP 0078 00)
Grommets (Item 7,WP 0081 00)
Wire Ties (Item20, WP 0078 00)
REMOVAL.
1. Remove two screws (1, Figure 1) from recording thermometer element (2).
CAUTION
To prevent damage to the thermometer element, do not bend or kink element tubing.
2. Separate thermometer element housing (2) from recording thermometer (3).
3. Drill out three drive rivets (4) and remove clamps (5) from thermometer element tubing (6).
4. Remove sealant from around grommet (7) and remove grommet. Discard grommet.
|