TM 55-8145-221-14&P 0006 00-15 Change 1 OPERATION UNDER USUAL CONDITIONS – Continued   0006 00 OPERATING PROCEDURES – Continued. CONTINUOUS OPERATION – (Figure 12). 1.     Monitor container temperature indication on recorder thermometer (1).  Make sure temperature is correct for type of cargo being stored in container. 2.     Check operation of generator set: a.     Open control panel door (2).  Door will not lift completely open.  Check COOLANT TEMP (3) [170-200F          (77-93C)] and OIL PRESSURE (4) [25-60 psi (172-414pKa)] indicators for normal readings. b.    Check AC Voltmeter (5); should indicate 208VAC.  Adjust VOLTAGE by adjusting potentiometer (6) if required. c.     Check frequency gauge (7); should indicate 60HZ.  Adjust frequency control knob (8) if required by first loosing locknut (9).  Tighten locknut when adjustment is complete. __________ WARNING High voltage is produced when this generator set is in operation.  Improper operation could result in personal injury or death. With any access door open, the noise level of this generator set when operating could cause  hearing  damage.    Hearing  protection  must  be  worn  when  working  near  the generator set while running. 3.     Monitor fuel level in fuel tank (10).  Add fuel as required. CONTROL PANEL SHOWN OPEN Figure 12.  Generator Set Operations Check PRESS TO RESET MASTER SWITCH PRIME & RUN AUX FUEL FUEL LEVEL BATTERY CHARGE 1/2 FUEL COOLANT TEMP OIL PRESSURE START OFF PREHEAT ENGINE TOTAL HOURS EMERGENCY STOP PUSH TO STOP OFF OPEN BATTLE SHORT VOLTAGE POWER ON OFF ON CLOSED PERCENT RATED CURRENT AC   VOLTS HOBBS QUARTZ PRIME & RUN AC CIRCUIT INTERRUPTER PANEL LIGHTS 100 140 180 240 8 4 PRESSURE AMPERS D.C. 0 -10 +10 +20 CHARGE DISCHARGE HERTZ 60  HERTZ PHASE L3-L1 L3-L0 VOLT AM-VM 8 9 2 4 3 7 5 6 10 1

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business