TM 55-8145-221-14&P
0006 00-15
Change 1
OPERATION UNDER USUAL CONDITIONS Continued
0006 00
OPERATING PROCEDURES Continued.
CONTINUOUS OPERATION (Figure 12).
1. Monitor container temperature indication on recorder thermometer (1). Make sure temperature is correct for type of
cargo being stored in container.
2. Check operation of generator set:
a. Open control panel door (2). Door will not lift completely open. Check COOLANT TEMP (3) [170-200F
(77-93C)] and OIL PRESSURE (4) [25-60 psi (172-414pKa)] indicators for normal readings.
b. Check AC Voltmeter (5); should indicate 208VAC. Adjust VOLTAGE by adjusting potentiometer (6) if
required.
c. Check frequency gauge (7); should indicate 60HZ. Adjust frequency control knob (8) if required by first
loosing locknut (9). Tighten locknut when adjustment is complete.
__________
WARNING
High voltage is produced when this generator set is in operation. Improper operation
could result in personal injury or death.
With any access door open, the noise level of this generator set when operating could
cause hearing damage. Hearing protection must be worn when working near the
generator set while running.
3. Monitor fuel level in fuel tank (10). Add fuel as required.
CONTROL PANEL SHOWN OPEN
Figure 12. Generator Set Operations Check
PRESS
TO RESET
MASTER SWITCH
PRIME & RUN
AUX FUEL
FUEL LEVEL
BATTERY CHARGE
1/2
FUEL
COOLANT TEMP
OIL PRESSURE
START
OFF
PREHEAT
ENGINE
TOTAL HOURS
EMERGENCY
STOP
PUSH
TO STOP
OFF
OPEN
BATTLE SHORT
VOLTAGE
POWER
ON
OFF
ON
CLOSED
PERCENT RATED
CURRENT
AC
VOLTS
HOBBS
QUARTZ
PRIME
& RUN
AC CIRCUIT
INTERRUPTER
PANEL
LIGHTS
100
140
180
240
8
4
PRESSURE
AMPERS
D.C.
0
-10
+10
+20
CHARGE
DISCHARGE
HERTZ
60 HERTZ
PHASE
L3-L1
L3-L0
VOLT
AM-VM
8
9
2
4
3
7
5
6
10
1
|