Table 2-1. Preventive Maintenance Checks and Services (PMCS) (Cont)
B - Before Operation
D - During Operation
W - Weekly
M - Monthly
Item
Interval
Item To Be Inspected.
Equipment is not
No.
Ready/Available if:
BDWM
Procedures
Door Gasket and Retainer
6
Gasket is worn or damaged.
With interior light switched on, close
door. There shall be no light visible
around door. Visually check gasket for
team, loose mounting, wear or aging.
Switch and Cover
7
Switch cover is damaged or
doesn't trip switch.
Check for cracks or breaks. (Models
AA60OPF, AA120OPFA, and AA400OPF).
Push switch to turn on or off to make
sure its working. (Models MDS1600N,
TKR-600C, and TKR-4000C) Toggle
switch to turn on or off to make sure its
working.