TM 9-4110-257-14
4-35.
BATTERY BT TESTING AND REPLACEMENT. - Continued
(3)
Pull the red (positive) shield (7) back to expose positive lug (8).
(4)
Loosen self locking nut (9) and carefully remove lug (8) from battery (6).
(5)
Remove four nuts (10), lock washers (11), and battery clamp (12). Discard lock washers.
WARNING
Battery can explode and cause injury to personnel and equipment if battery is
dropped or punctured. Do not lift battery by terminals.
(6)
Remove battery (6) and four L-bolts (13).
(7)
Remove ten bolts (14), lock washers (15) and battery frame (16). Discard lock washers.
c.
Installation.
(1)
Install battery frame (16), ten bolts (14) and new lock washers (15).
WARNING
Battery can explode and cause injury to personnel and equipment if battery is
dropped or punctured. Do not lift battery by terminals.
(2)
Position four L-bolts (13) in the battery frame (16). Install battery (6).
(3)
Install battery clamp (12) over L-bolts.
(4)
Install new lock washers (11) and nuts (10).
WARNING
Battery explosion and personal injury can occur if positive lug is not installed first
or if battery posts are shorted.
(5)
Install positive lug (8) using tag and wiring diagram (fig. 1-4) and tighten self locking nut (9).
Cover lug with red (positive) shield (7). Remove tag.
(6)
Install negative lug (4) using tag and wiring diagram (fig. 1-4) and tighten self locking nut (5).
Cover lug with black (negative) shield (3). Remove tag.
NOTE
FOLLOW-ON MAINTENANCE:
Close right side condenser door.
Put unit back into service.
4-90
|