TM 9-4110-257-14
5-6.SERVICE MANIFOLD INSTALLATION.
This task covers:
a. Installation
b. Removal
INITIAL SETUP
Tools:
Refrigeration Unit Service Tool Kit
4, Section III, Appendix B
Refrigerant Recovery and Recycle Unit
5, Section III, Appendix B
Equipment Conditions:
Refrigeration unit shut down (para. 2-7) and battery disconnected (para. 4-35).
Right front bottom door open.
Right side condenser door open.
General Safety Instructions:
WARNING
Rotating parts are used in the refrigeration unit. Personal injury can
result if battery is connected.
Dangerous chemical refrigerant under pressure is used in the
operation of this equipment. Use great care to avoid contact with
liquid refrigerant. Work in a well ventilated area.
General Safety Instructions:
WARNING
Sudden and irreversible tissue damage can result from freezing.
Wear gloves and face protector or safety glasses in any situation
where skin or eye contact with refrigerant is possible.
Heat may cause the refrigerant to decompose and release irritating,
toxic, and corrosive gases. Prevent contact of refrigerant with flame
or hot surfaces.
Compressor lubricating oil used in this refrigeration system is
caustic. Wear gloves and a face protector or safety glasses in any
situation where skin or eye contact is possible. If oil does contact
skin, wash with soap and water.
a. Installation.
CAUTION
Using excessive force when opening or closing valves can cause
damage to the valve seats.
NOTE
The compressor shut off valves can be adjusted to three positions, fully
closed to block the refrigerant tubes and isolate the compressor and
service port, fully open to allow flow from piping to compressor but not
the service port, and cracked (one turn closed from fully open) to allow
flow from piping to compressor and service port on valve.
(1) Remove two shut off valve caps and turn the shut off valves fully counterclockwise to backseat them.
5-8
|