TM 9-4110-257-14
5-15.
COMPOUND GAGE REPLACEMENT. - Continued
b.
Installation.
(1) Wrap anti-seize tape around compound gage (6) connector threads.
(2) Install compound gage (6), three bolts (5), and new self locking nuts (4).
(3) Install coupling (3).
(4) Align copper tubing (2) and connect flare nut (1) to coupling (3).
(5) Seal any openings in back of compound gage (6) case with silicone RTV.
NOTE
FOLLOW-ON MAINTENANCE:
Close left side condenser door.
Replace dehydrator (para. 5-14).
Leak check (para. 5-10), evacuate (para. 5-11), and charge (para. 5-12) the refrigeration system.
5-34
|