TM 9-4110-257-14
5-19.
CONDENSER COIL REPLACEMENT
This task covers:
a. Removal
b. Installation
INITIAL SETUP
Materials/Parts:
Self Locking Nuts (8)
17, Appendix G
Self Locking Nuts (10) (Various Clamps)
12, Appendix G
Equipment Conditions:
Refrigeration system discharged (para. 5-7) and purged (para. 5-8).
Both side condenser doors open.
Condenser coil guard removed (para. 4-19).
a. Removal.
(1) Remove self locking nut (1) and bolt (2). Discard self locking nut.
(2) Purge (para. 5-8) and debraze (para. 5-9) two fittings (3) from condenser coil (4).
WARNING
Coil fins are sharp and can cut hands or fingers. Wear gloves to prevent
personal injury when handling coil.
(3) Remove eight self locking nuts (5), bolts (6), and condenser coil (4). Discard self locking nuts.
(4) If condenser shroud (7) must be replaced, remove fan drive shaft (para. 5-4).
(5) Remove nine self locking nuts (8), bolts (9), and condenser shroud (7). Discard self locking nuts.
b.
Installation.
(1) If condenser shroud (7) was removed, install shroud, aline clamps (10) and install nine bolts (9) and new self
locking nuts (8).
(2) Install fan drive shaft (para. 5-4).
5-41
|