TM 9-4110-257-14
Table 2-1. Operator Preventive Maintenance Checks and Services for Model F10000RD-Continued
Location
Item
Item to
Not Fully Mission
No.
Interval
Check/
Procedure
Capable if:
Service
Refrigeration
Unit Interior
WARNING
Exposed rotating parts are contained in
the refrigeration unit. Care must be
taken when doors are open to prevent
personal injury.
39
Monthly
Dehydrator
Inspect the dehydrator for damage or evidence of
Dehydrator is damaged
refrigerant leak. If damaged or evidence of
or evidence of leak is
leaking found, notify direct support maintenance
found.
to replace it.
40
Monthly
Receiver
Inspect the receiver for damage and evidence of
Receiver is damaged or
refrigerant leak. Inspect the isolation valves for
evidence of leak is
evidence of refrigerant leak. If damaged or
found.
evidence of leaking found, notify direct support
maintenance to replace it.
41
Monthly
Pressure
Inspect the pressure regulator valves for damage
Pressure regulator valve
Regulator
or evidence of refrigerant leak. If damaged or
damaged or evidence of
Valves
evidence of leaking found, notify direct support
leak is found.
maintenance to replace it.
42
Monthly
Metal Hose
Inspect the metal hose assemblies for kinks or
Metal hose assembly
Assemblies
evidence of refrigerant leak. If damaged or
kinked or evidence of
evidence of leaking found, notify direct support
leak is found.
maintenance to replace it.
43
Monthly
Valves
Inspect the valves for evidence of refrigerant
Evidence of leak is
leak. If evidence of leaking found, notify direct
found.
support maintenance to replace it.
44
Monthly
Check Valve
Inspect the check valve for evidence of
Evidence of leak is
refrigerant leak. If evidence of leaking found,
found.
notify direct support maintenance to replace it.
2-21
|